Industrial energy infrastructure

Procuring storage
should not be an
engineering project.

We curate the single highest-performing BESS architecture globally. No marketplaces. No broker fees. Just deployment certainty.

Months.
Logistics guarantee

Delivered Duty Paid.
To your foundation.

From manufacturing allocation to final site placement, we manage all shipping, multi-jurisdictional customs, and tax liabilities. You pour the pad; we drop the system.

IncotermsStrictly DDP
Lead time≤ 6 months
Industrial 20-foot BESS container — neutral studio rendering
Asset lifecycle

Comprehensive coverage.
Zero capex surprises.

A storage system is only as viable as its degradation curve. Ten years of hardware and performance coverage are baked into the unit price. Performance guarantee: 69.7% SoH at 8,000 cycles or 10 years.

Duration120 months
CoverageDefect + degradation
Years.

We don't broker.
We commit.

The problem with choice

Marketplace listings normalise dozens of OEMs onto comparable spec sheets, hiding sub-component variance behind unified columns. Buyers end up evaluating incompatible systems, taking on integration and delivery risk that doesn't show up until the project is already running.

Our mechanism

Our engineering team continuously evaluates the global supply chain against real deployment data.

We commit to the single highest-performing LFP system available worldwide and lock in delivery and warranty terms on your behalf. You don't get a list of speculative options. You get the definitive answer to industrial-scale storage.

Active architecture

Current default specification

System

Cell chemistry
LFP — Lithium Iron Phosphate
Container format
20-foot HC, DC liquid-cooled
Energy per container
5.0 MWh @ 0.5C
Power per container
≤ 2 × 1.25 MW
DC voltage range
1164.8 – 1497.8 V

Performance

Cycle life
≥ 8,000 cycles@ 0.5C / 0.5C
DC round-trip efficiency
96% @ 0.25C · 95% @ 0.5C
System RTE
≥ 87.66%
Depth of discharge
90.0%
Reaction time
< 500 ms
Ramp-up time
< 1 s
System availability
≥ 98.20%
Performance guarantee
69.7% SoH @ 8,000 cycles or 10 years

Environment & enclosure

Operating temperature
−30 to +60 °Cde-rated > 40 °C
Maximum altitude
< 2,000 m
Ingress rating
IP67 module · IP54 container · IP55 PCS
Thermal management
DC liquid cooling
Anticorrosion
C4H standard · C5 optional

Safety & fire

Suppression
Aerosol-based active suppression
Detection
Photoelectric · thermal · smoke
Fire control
Central panel with fire-brigade link

Certifications

Battery system
UL 1973 · UL 9540 · UL 9540A · IEC 62619 · IEC 62620 · UN 38.3 · NFPA 855
PCS
UL 1741 · IEC 62109-1/2 · G99 · NEC 2020 · IEC 62116 · VDE 4110 · EN 50549-2 · IEC 60529 · IEC 61000-6-2
Cyber security
EU NIS2 directive compliant

Control & integration

SCADA / EMS
Siemens WinCC OA on RTU
Communication protocols
Modbus · RS485 · IEC 104
Transport
Ethernet · LTE · fiber

Specifications represent the baseline architecture currently procured via BESS Integrator. Project-specific configurations may yield variations within the selected OEM capability matrix.

Secure your allocation.

Start project intake

Response SLA: under 24 business hours.